ELECTRONIC TIMERS AT48 - SERIES
 
Technical Data
Supply voltages 110, 230 VAC, 50/60Hz
110,220 VDC
Supply voltage tolerance: ±10%
Operating modes: ON Delay, Interval ON,
Cyclic equal with relay OFF first,
Cyclic equal with relay ON first.
Timer range: 3,15,60S (Seconds)
3,15,60M (Minutes)
3H (Hours)
Accuracy setting +/- 5% of full scale
Repeat accuracy Much better than 0.5%
Reset time 0.1 second
Terminals 8 Pin base or 10 Pin screw terminal base.
Operating temperature 0°C t o 50°C at relative humidity 85%
Storage temperature -10°C t o 75°C
Enclosure material UL94-VO impact resistant ABS (Black)
Relay contact rating 2 C/O contact rated for switching
5A@ 230V AC/ 24V DC
Mounting Panel mounting using 2 metallic clamps
Cut- out size 45 (W)x45(H)
Power consumption 3VA at 230V AC
Life expectancy Mechanical 2 x 10` operations
Electrical 1 x 105 operations
(maximum no. of operations 1200/hours)
 
8 Pin base
Mode Ordering code
Delay on energise AT 48 B DE()*
Interval on AT 48 B IT()*
Cyclic relay off first AT 48 B CD()*
Cyclic relay on first AT 48 B CY()*
 
Previous123456789101112131415161718Next